THE EFFECT OF TEMPERATURE AND WATER CONDUCTIVITY IN HOT BASIN TOWARD EFFECTIVENESS OF COOLING TOWER ON UTILITY UNIT PT. X

Authors

  • Indah Dhamayanthie Institut Teknologi Petroleum Balongan, Indramayu , Indonesia
  • Yully Mulyani Institut Teknologi Petroleum Balongan, Indramayu , Indonesia

DOI:

https://doi.org/10.33603/jgst.v7i1.11

Abstract

PT X is one of the Reviews largest ethanol producing plant in Indonesia, PT X located ± 15 km the northeast of Solo or 110 Km to the south of Central Java, SeAprilang. Cooling Tower is a tower or building of water circulation directly or indirectly contact with hot water and then converted into cold water expected that a number of heat from a fluid to another fluid. The Cooling Tower operates According to the diffusion principle, where temperature changes can result in a difference in the rate of temperature displacement. From the process in the cooling tower unit there are Several variables contained in the cooling towers ranging from the temperature and water conductivity in the hot basin. Obtained from the variables can be used to analyze the effectiveness of the cooling tower unit. When the conductivity contained in the water in the basin of hot high then the effectiveness of cooling tower will Decrease, likewise vice versa. And the value of effectiveness Obtained range of 76.12% - 87.80%. Where the company's standard value is 75% effectiveness. There are Several factors Determining the high value of conductivity values such as chemical mixing, high temperature in the cooling tower, and the temperature around the cooling tower.

References

Siallagan, PriAprily H, 2017, "Performance Analysis At the CT01 8330 Cooling Tower Water Treatment Plant-2 PT Krakatau Steel.Tbk". Journal of Mechanical Engineering (JTM): Vol. 06, No. 3 June 2017. ISSN 2549-2888

Handoyo, Yopi 2005, "Performance Analysis of Cooling Tower LTC 400 At XYZ". Imiah Journal of Mechanical Engineering, Vol. 3, 1 February 2015, Universitas Islam 45 Bekasi.

Stanford III, Herbert, 2012, "HVAC Water Chiller And Cooling Tower Fundamentals, Application, And Operation" .CRC Press: London, England.

Musini, Ahmad and Zicko P, "Effectiveness Analysis Engine Cooling Tower Using Range and Approach". OPTIONS Journal Vol 11 # 2 December 2018. ISSN 1693-2102

Gumilar, Arie. 2011. Cooling water systems.Jakarta: STE

Hensley, John C., 2009, "Cooling Tower Fundamentals". SPX Cooling Techonologies Inc., Kansas.

Energy Efficiency Guide for Industry in Asia. 2001. Indian Institute of Technology Kanpur, India.

Babcock Glenn A, “Because Temperature Matters: Maintaining Cooling Towers, Baltimore Air coil Company., RSES USA.

Ahluriza, Nazaruddin S.,2021, “Review of the Effect of Range and Approach on Tower Effectiveness Cooling Unit 2 PT. Indonesia Power Kamojang”. Vol. 13, No. 2, Juli – Desember, Universitas Diponegoro. Semarang.

Anugrah Setiya A, Firmansyah., 2021, ”Performance Analysis of Natural Draft Cooling Tower in Development Center Refinery Unit Oil and Gas Human Resources Earth” Pusat Pengembangan SDM Minyak dan Gas Bumi, Swara patra

Downloads

Published

2023-08-22

Citation Check